The Mercury online UPS series offers high frequency, double-conversion technology uninterruptible power supply systems that provide maximum power protection for mission-critical equipment. Such equipment require always-on power supply, with zero switching time, which only online power backup systems can provide. Moreover, they also need the purest quality of power, of pure sine wave. The Mercury online UPS provide that ideal power backup supply for critical, sensitive equipment, ensuring, too, that they are protected from power problems in the AC line.

Key Features

  • Application: network, servers and other IT equipment
  • High frequency and double conversion on-line technology
  • Fully digitised microprocessor control
  • Wide input voltage range
  • UPS startup without battery
  • Cold start
  • Advanced battery management
  • Advanced battery charge in UPS off mode
  • Lightning and surge protection
  • Short circuit and surge protection
  • Fan speed auto control when loads varies
  • Optional extension battery pack
  • Load capacity display
  • Smart RS232 communication with monitoring software
  • Optional SNMP Card slot
Power
Power 10KVA / 7000W
Voltage range 176 ±5VAC~276 ±5VAC,
Frequency 46~54Hz ±0.5Hz, or 56~64Hz ±0.5Hz auto sensing
Input phase Single phase
Power factor ?0.98
Voltage range 220VAC ±1%
Output phase Single phase
Frequency 50Hz ±0.2% (battery mode)
THD < 2% (Linear load); < 6% (non-Linear load)
Overload 105%~130% 10min turn to Bypass mode,
> 130% 1s turn to Bypass mode
Crest factor 3:1 (max)
Waveform Pure sine wave
Transfer time 0ms (AC mode - Battery mode)
0ms (AC mode - Bypass mode)
Efficiency ?88%
AC mode 5 cycles turn off inverter, no transfer to Bypass,
provide alarm.
Battery mode 5 cycles turn off inverter, provide alarm.
Bypass mode Input fuse blown or break action.
Battery Model 12V sealed lead acid maintenance free
DC voltage 240VDC
Configuration 20x 12V/8.2AH
Backup time 13min (half load) / 5min (full load)
Charge current 1A (standard unit) / 5A (long time unit)
Recharge time 90% capacity after 8hrs charging
Communication Interface RS232; SNMP (optional)
Parallel Port Parallel availability for redundancy and load sharing up to three unit
LCD Indication Input voltage/frequency; battery voltage; output voltage/frequency; load watt/VA value & percent; inverter temperature; operation mode such as “on batt” or “on bypass”
LED Indication Green: normal operation; Yellow: warning condition
Red: abnormal operation
Noise level ? 55dB
Temperature 0~40?C; 0 ~ 40?C (storage temperature)
Humidity 0~95% (non-condensing)
Altitude < 1500m
Weight Net/Gross 92/107kg (standard unit); 36/51kg (long time unit)
Dimension (WxDxH) 270 x 570 x 720mm
Packaging (WxDxH) 370 x 670 x 940mm